Cast-in fire collar

H65S 65mm Cast-in Fire Collar

The smallest collar in the range, sized for small-bore plastic pipe penetrations up to 63mm, such as appliance and branch wastes. Cast into the slab before the pour and sealed by patented spring activation, restoring the floor’s fire resistance where a pipe passes through it.

  • LPCB certified
  • Slabs 150mm thick and up
  • Patented spring activation
Sure Snap H65S 65 mm cast-in fire collar

Fire performance

Assessed fire resistance by pipe type

Every configuration below, installed in a concrete or metal deck slab, is assessed to BS EN 1366-3 in CSIRO report FCO-3646. Each rating covers integrity (E), which holds back flames and hot gases, and insulation (I), which limits the temperature rise on the side away from the fire. Ratings are in minutes.

The table below is a summary. For the full assessment, including ratings above 2 hours, use the Sure Snap Product Selector.

Swipe to see all columns →

Pipe typePipe standard / brandPipe size × wall thickness (mm)Fitting in collarFire ratingFCO-3646 reference
PVCPVC-U / PVC-C pipea20, 25, 32, 40, 50, 63
Wall 1.5 to 4.7mmb
YesEI 120Table 6.6.1 (p.22)
Table 6.6.2 (p.23)
HDPEHDPE pipea25, 32, 38, 40, 44, 50, 56, 57, 63
Wall 2.3 to 5.8mmb
No;
butt weld allowedc
EI 120Table 6.6.3 (p.24)
HDPEGeberit Silent-DB20 (PE-HD)56 × 3.2
60 × 3.2
70 × 3.6
NoEI 120Table 6.6.11 (p.30)
PPMecflow (PP-R)20 × 2.8
25 × 3.5
32 × 4.4
40 × 3.7
50 × 4.6
63 × 5.8
NoEI 120Table 6.6.10 (p.29)
PPRehau Raupiano40 × 1.8
50 × 1.8
75 × 1.9
Yes (DN 40 and 50 only);
butt weld allowedc
EI 120Table 6.6.7 (p.27)
Table 6.6.8 (p.28)
PPValsir Triplus40 × 1.8
50 × 1.8
70 × 2.6
Yes (DN 40 and 50 only);
butt weld allowedc
EI 120Table 6.6.5 (p.25)
Table 6.6.6 (p.26)
PE-XEN ISO 15875-216 × 2.2 (nominal 12)
63 × 8.6 (nominal 50)
NoEI 120Table 6.6.4 (p.25)

Swipe to see all columns →

Sizes are nominal pipe sizes in mm, shown as size × wall thickness.

Minimum 150mm concrete slab.

  1. Approved pipe standards:
    PVC-U: EN 1329-1, EN 1453-1, EN ISO 1452-2, EN ISO 15493
    PVC-C: EN 1566-1, EN ISO 15493, EN ISO 15877-2
    HDPE: EN 12201-2, EN 12666-1, EN 1519-1, EN ISO 15494
  2. The approved wall thickness range varies with pipe size – confirm a specific size and wall thickness with the Sure Snap Product Selector or the FCO-3646 tables.
  3. A butt-welded joint may sit inside the collar, provided the weld bead plus the pipe wall is no thicker than FCO-3646 allows (variation f).

Sealing the annular gap (per FCO-3646)

Up to 12mmNo sealant or grout required
Up to 20mmMin. 10mm of Snap Fire Seal FRAS, or min. 30mm of non-shrink grout (or down to the rubber ring), or min. 50mm of non-combustible Rockwool with min. 5mm of sealant on top
Over 20mmMin. 60mm of non-shrink grout (or down to the rubber ring), or min. 50mm of non-combustible Rockwool with min. 5mm of Snap Fire Seal FRAS on top
Over 50mmMin. 60mm of non-shrink grout (or down to the rubber ring)

Backing for the sealant can be cardboard, mineral wool or PE foam. Full method in the installation guide.

For full coverage and fire ratings greater than 2 hours, see CSIRO Assessment Report FCO-3646.
Not sure your installation is covered? Use the Sure Snap Product Selector or contact our technical team.

Specifications

H65S specifications

Stock codeH65S-RR
Inner Ø79mm
Standard collar height250mm (trim on site; 50mm extensions)
Base flange168mm round
CasingPolypropylene
Activation springs3 made of galvanised steel
IntumescentPatented Intumesh, mesh-backed sheet
AccessoriesStackable extensions
LPCB certificate1833a/01